Dry pendent 10 year test dry pendent 10 year test jjmoore73 mechanical op 12 jun 13 20 11.
Dry pendent sprinkler head testing.
Dry sprinklers are designed for use in areas where the sprinkler may be subjected to freezing conditions.
Dry sprinklers may be used in dry systems where the entire area being protected is subject to freezing and wet systems where a small portion of the area being protected is subject to freezing.
The standard way to sprinkle exposed building areas such as an open garage freezer storage or unheated spaces is to install a dry pipe sprinkler system.
What would be considered a sample.
At the ampule s rated temperature the sprinkler opens releasing the.
We take great pride that globe solutions supply critical life safety applications and remain committed to supporting your construction needs during these challenging times.
These sprinkler heads need to be tested every 10 years.
The globe gl series dry type pendent sprinkler utilizes a frangible glass ampule sprinkler.
For instance in a 3 story apartment.
Nfpa 25 standard for the inspection testing and maintenance of water based systems.
Nfpa 25 section 5 3 1 2 states a representative sample of sprinklers for testing shall consist of a minimum of not less than four sprinklers or 1 percent of the number of sprinklers per individual sprinkler sample whichever is greater.
Globe fire sprinkler remains open for business and focused on the health and safety of our employees while continuing our commitment to our customers.
Per nfpa 25 after 10 years in service a sample of dry sprinkler heads are required to be tested by a recognized laboratory acceptable to the ahj for field service testing.
Dry sprinklers dry sprinkler order form.
Model esfr 17 dry type pendent sprinklers early suppression fast response 16 8 k factor series ds 1 dry type sprinklers pendent upright and horizontal sidewall standard response standard coverage k factor 5 6k series ds 1 dry type sprinklers pendent upright and horizontal sidewall.
Despite their advantages be aware that dry pipe sprinklers have separate maintenance testing and installation requirements to ensure proper performance.
The globe gl series dry type pendent sprinkler is designed for use in special applications such as freezing environments and conditions where sediment or foreign materials might accumulate in ordinary drop nipples.
Dry pendant pattern sprinkler heads those with a dry drop pipe section should be tested every five years or less unless stated otherwise by the manufacturer 5 or 20 heads of each batch of dry pendant patterned sprinklers installed on the site whichever is the greater should be tested.